Alpha Technologies Cordex Controller Ver.3.1x User Manual
Page 86
0700015-J0 Rev B
84
6.7.3.4 Example One – Logging Three Phase Voltage Input (Rectifier System)
The following is an example of a Data Log configured to monitor the voltage input for a two phase rectifier
system.
1. From the web interface, select
Signals > Configure Data Logging
.
2. Under
Data Log Files
, select an unused log file to edit.
3. Enter a filename description under
File Information
.
4. Enter the number of
Log Records
you want to keep and select
FIFO
as the
File Save Option
.
5. Under
Start Trigger
and
Stop Trigger
, select
Manual
for each.
6. Under
Log Frequency
, select
Enable Time Interval
and enter 600 seconds (10 minutes).
7. Click the
Log Signals
button to select the rectifier signals for logging.
8. Select
Rectifier Signals
from the Signal List in the Configure Signals window.
9. Scroll down and check each phase box as shown.
10. Click the
Apply
tab (to accept changes and return to Configure Data Logging window).
11. Click the
Save
icon to save the changes and click Accept when prompted.
12. Start the log by clicking the
Start
button located next to the File Information heading (see Figure 95.
Once the data has collected for the desired interval, return to this window and click the
Stop
button.
13. Select
Logs & Files > Retrieve Logs
. Select the file name from the pull-down menu and then select
Data Log
to view the log information in a new window. Copy and paste the data into a spreadsheet
application for analysis.
Figure 95 — Configure (Signals) Data Logging web interface window, example one
Figure 96 — Enable (Rectifier) Signals for Data Logging