6.7 Signals
This menu category consists of system identifiers and calibration controls. Parameters can be set/ac-
cessed such as controller signals, rectifier signals, analog and digital inputs. With the web interface, data
logging can be configured.
6.7.1 Calibrate Analog Inputs
This menu item provides a direct link to the Analog Inputs menu heading; which may also be accessed
via the menu item Configure Signals, see 6.7.2.
6.7.1.1 Overview of Analog Input Channels
The majority of the CXC analog input channels are each designed to accept a specific input signal.
2.1 summarizes the analog input channel assignments; which may vary depending on the hardware con-
figuration (list options):
√
=
Installed
BiV
=
-60 V to +60 V
I
=
-50 mV to +50 mV
T
=
-55ºC to +100ºC (powered)
V
=
0 to 60 V
X
=
Not Installed
Table E — Analog input channel assignments
Channel
List Option
CXCU
Assignment
120
121
122
123
124 125
129
V1
√
√
√
√
√
√
√
X
V2
√
√
X
√
√
√
√
√
GP1
T1
T1
T1
T1
V3
T1
T1
T1
GP2
T2
T2
T2
T2
V4
T2
T2
T2
GP3
X
T3
X
T3
V5
BiV
T3
X
GP4
BiV
T4
BiV
T4
T1
BiV
T4
X
I1
√
√
√
√
√
√
√
√
I2
X
√
X
X
X
√
√
X
I3
X
X
X
X
X
√
√
X
I4
X
X
X
X
X
√
√
X