This feature is found under the Global Alarm Configuration menu (submenu of Alarms) and the tone is
enabled by default. The Supervisor can enable/disable the audible alarm buzzer (tone).
6.6.9 Configuring ALCO
This feature is found under the Global Alarm Configuration menu (submenu of Alarms), see Figure below:
ALCO Duration
Duration in minutes, that all ALCO enabled alarms are affected by the
parameters set for this feature. (For LCD interface, tap on the number to
edit via a virtual numeric keypad.)
Enable ALCO Duration
Activates the ALCO Duration feature.
Silence Buzzer
Diables the audible alerts for ALCO enabled alarms.
Revert Relays
Activating ALCO for the alarm will revert the relay status to its normal
state.
Stop Sending Email
Stops transmission of Email communications
Stop Sending SNMP Traps Stops transmission of SNMP traps. SNMP still works, but is no longer
sending traps.
Figure 70 — Global Alarm Configuration – Web
Toggle the check box to select
Discard changes and return to
previous screen
Sliders and scroll bars are used for
navigation
Select menu item to configure
Accept changes and return to
previous screen
Figure 71 — Configure ALCO – LCD