GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 70

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
70
Disconnect
Reconnect
7.
Slope Thermal Compensation
Slope thermal compensation information, if implemented in the system, should
be recorded, so that it can be programmed when the new controller has been
installed.
Record this information by selecting the following menus from the front panel
display: MENUÆ CONFIGÆ STC
STC Enabled/Disabled
Nominal Temperature
Step Temperature
Disconnect Temperature
Low Temperature
Upper Temperature
Raise Voltage Enable
Temperature Units
8.
Rectifier Float Setpoints
Rectifier float setpoint determines the system voltage.
Record the float setpoint by selecting the following menus from the front panel
display: MENU ÆCONFIGÆ RECT MANAGER
Plant V
I limit
SHVSD
9.
Securing Contactors
If Battery and Load contactors are in the system, contactor control boards
should be configured so that they do not OPEN during the controller
replacement. To ensure that these contactors do not open, force all LVLD and
LVBD contactors closed.
NOTE: These contactors may have already been forced closed per customer
requirements. If so, then proceed to the next step.
To force LVLD contactors closed, place SW300 in the up position as shown in
figure 6-2 and 6-3.