rectifiers. Move the cursor to the field and
use the <+> or <-> key to adjust the threshold
value. Press
6.
Batteries
Model
The configuration of this field selects the
installed battery type from a list of pre-
defined battery types used in reserve time
prediction and enhanced battery test features.
Move the cursor to the field and use the <+>
or <-> key to adjust the threshold value. Press
Strings
The
configuration
of this field selects the
number of battery strings in the system. This
parameter is used in reserve time prediction
and enhanced battery test features. Move the
cursor to the field and use the <+> or <-> key
to adjust the threshold value. Press
to save the change.
Cells/String
The configuration of this field selects the
number of installed cells in the battery strings.
This parameter is used in reserve time
prediction and enhanced battery test features.
Move the cursor to the field and use the <+>
or <-> key to adjust the threshold value. Press
Type
The configuration of this field selects the
batter type, Flooded or Valve Regulated
(sealed). This parameter is used in reserve
time prediction and enhanced battery test
features. Move the cursor to the field and use
the <+> or <-> key to adjust the threshold
value. Press
7. Thermal
Comp
This feature allows dynamic control of sealed