GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 57

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
57
from this screen.
Contactor
1-3
Type
This setting identifies the type of contactor,
BATTERY, LOAD or NONE that has been
installed in the plant. Be sure that the wiring
for the contactor being configured matches
the type chosen here. For standard GPS
configurations using BIC cards, Contactor 1 is
wired to and controls all BATTERY
contactors in the plant. Contactors 2 and 3 are
wired to and control only LOAD contactors.
To toggle between the various contactor
types, move the cursor to one of the fields and
use the <+> or <-> key to select the desired
type. Press
Disconnect
This setting configures the plant voltage at
which the contactor will disconnect from the
bus. Use the <+> or <-> key to adjust the
voltage to the desired level. Press
to save the change.
Reconnect
This setting configures the plant voltage at
which the contactor will reconnect to the bus.
To prevent the contactor from re-operating
when battery voltage increases due to load
removal, a voltage several volts higher than
the disconnect voltage is recommended. Use
the <+> or <-> key to adjust the voltage to the
desired level. Press
change.