General specifications – GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 11

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
11
General Specifications
Basic Millennium II specifications are summarized in table 2-B. Consult service center
for other details.
Table 2-B: General Millennium II Controller Specifications
General
Specifications
Input Voltage Range
±24 Vdc, -48 Vdc (Range: 18-60V)
Maximum Input Power
36W depending upon options
Operating Temperature Range
-40 to 75 °C (-40 to 167 °F)
Storage Temperature Range
-40 to 85 °C (-40 to 185 °F)
Physical Specifications
9.24 in. H, 20.76 in. W, 2.14 in. D
Display
8-line by 40-character backlit LCD
Cabinet Mounting Requirements
Door mounted
Input/Outputs
Specifications
Form C Alarm Output Contact Ratings
60VDC at 0.5A
Plant Voltage Measurement
Accuracy
0 to 50 °C (±.05% of full scale + 1
count)
-40 to 85 °C (±0.1% of full scale + 1
count)
Resolution
48V Systems: ±40 mV
24V Systems: ±25 mV
48V Systems: ±70 mV
24V Systems: ±40 mV
0.01V
Plant Current Measurement (Up to 2
shunts)
Accuracy
Resolution
0 to +50 °C : ±0.5% of full scale
-40 to +85 °C: ±1.25% of full scale
1A
Temperature Measurement
Accuracy
Thermistor temperature
One-Wire Serial probes
Resolution
-5 to +55 °C: ±2°C
-40 to +85 °C: ±3°C
-5 to +55 °C: ±1°C (next release)
-40 to +85 °C: ±3°C
0.1°C
4-20mA Input Monitor
Accuracy
Resolution
±100µA
±10.0µA
General (0-5V) Input
Accuracy
0 to +50 °C: ±0.5% of full scale