GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 41

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
41
Voltage Threshold Ranges and Default Values
Table 4-I: Voltage Threshold Ranges and Default Values
Low
High
Default
Very Low Voltage (VLV)
24V
20.00 25.50 23.00
48V
40.00 51.00 46.00
Battery on Discharge (BD)
24V
Float
23.00 28.00 25.00
24V
Boost
23.00 28.00 25.00
48V
Float
46.00 55.00 51.00
48V
Boost
46.00 55.00 51.00
High Float Voltage (HFV)
24V
Float
24.75 29.75 26.50
24V
Boost
25.75 31.75 26.50
48V
Float
50.00 60.00 53.00
48V
Boost
52.00 60.00 53.00
High Voltage Shutdown Alarm (HV)
24V
Float
24.75 29.75 26.8
24V
Boost
25.75 31.75 26.8
48V
Float
50.00 60.00 53.6
48V
Boost
52.00 60.00 53.6
Rectifier On Threshold (ROT)
24V
20.00 25.00 22.00
48V
40.00 51.00 44.00
Controller Alarm Severity, LED and Relay Default Values
Table 4-J:Controller Alarm Severity, LED and Relay Default Values
Symbol Default
Designation
Default
Severity
Default LED Default
Relay
AAC ACO
Active
RO
None
None
ABS
Alarm Battery Supply Fuse
Major
CTLR
CTLR
AMJ Auxiliary
Major
Major None None
AMN Auxiliary
Minor
Minor None
None
ATA
Alarm Test Active
RO
None
None