GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 43

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
43
Symbol Default
Designation
Default
Severity
Default LED Default
Relay
HFV High
Float
Voltage
Minor RECT None
HVA High
Voltage
Major RECT HV
LMR
Limited Recharge
Minor
RECT
None
LVD
Low Voltage Disconnect
Minor
BAT
None
LVDA
Low Voltage Disconnect Fail
Minor
BAT
None
MCM Major
Communication
Fail Minor
CTLR
None
MDF Module
Failure
Minor RM
None
MOR
Measurement Out Of Range
Minor
RM
None
MTC
Module Type Conflict
Warning
None
None
NNC
Number Not Configured
Warning
None
None
OSA Open
String
Minor BAT
None
PFD
Password At Default
Warning
None
None
PGI
Program Line Invalid
Major
None
None
PHT Processor
Halt
RO
None None
POR
Number Did Not Respond
Warning
None
None
RLS1 Redundancy
Loss
Ninor
RECT None
RPI Rectifier/Plant
Inconsistency
Warning
None None
RTL
Reserve Time Low
Minor
BAT
None
SNC
Shunt Not Configured
Warning
None
None
STF
Self Test Failed
Minor
CTLR
CTLR
TPA
Thermal Probe Failure
Minor
CTLR
CTLR
URC User
Relay
Conflict
Warning None
None
VLA
Very Low Voltage
Critical
BAT
UR3
VSF Sense/Control
Fuse
Major CTLR CTLR
ZID
ID Not Configured
Major
RECT
None