Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
101
Enabled if Millennium was 1
Disabled if Millennium was 0
SW203-5 Full
Access
through
Aux Port
Using the front panel, go to:
MenuÆConfigÆComm PortsÆAux Port
Config Write to:
Enabled if Millennium was 1
Disabled if Millennium was 0
SW203-4 Full
Access
through
Modem Port
Using the front panel, go to:
MenuÆConfigÆComm PortsÆModem
Port
Config Write to:
Enabled if Millennium was 1
Disabled if Millennium was 0
SW203-3 Modem/Local/Aux
Setting Config
Set SW202-7 to:
0 if Millennium was 0
1 if Millennium was 1
SW203-2 Local
Port(Event
Log or Terminal)
Using the front panel, go to:
MenuÆConfigÆComm PortsÆLocal Port
Config Application to:
Event Log if Millennium was 1
Terminal if Millennium was 0
SW203-1
Aux Port(RS232 or
RS485)
Set SW202-5 to:
0 if Millennium was 0
1 if Millennium was 1
SW204(4-8) NOT USED
Not Applicable to Millennium II
SW204-3 Enhanced
Remote
Security
Set SW202-6 to:
0 if Millennium was 0
1 if Millennium was 1
SW204-2
Remote Alarm Test
Not Used
SW204-1 Rectifier
Energy
Management
Using the front panel, go to:
MenuÆConfigÆPlant
Config Efficiency to:
Enabled if Millennium was 1
Disabled if Millennium was 0