GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 42

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
42
Symbol Default
Designation
Default
Severity
Default LED Default
Relay
ATB
Alarm Test Aborted
RO
None
None
ATF
Alarm Test Failed
Warning
None
None
BBL
Memory Backup Battery Low Warning
None
None
BCA
Battery Type Conflict
Warning
None
None
BDA Battery
on
Discharge
Major BD
BD
BFA
Battery Test Failed
Minor
BAT
None
BID
Bay Interface ID Conflict
Major
CTLR
CTLR
BTA
Battery Test Active
RO
BD
BD
BTJ
Battery Thermal Major
Major
BAT
None
BTN
Battery Thermal Minor
Minor
BAT
None
CCH Configuration
Changed
RO
None
None
CDFA
Converter Distribution Fuse
Major
RECT
MJF
CDID Converter
ID
Conflict
Major
RECT
None
CFA Converter
Fail
Minor RECT None
CLC Clock
Changed
RO
None None
CMA
Minor Communications Failure Minor
CTLR
None
CMFA
Multiple Converter Fail
Major
RECT
None
CNF1 Contactor
1
Failed
Major
BAT
None
CNF2 Contactor
2
Failed
Major
BAT
None
CNF3 Contactor
3
Failed
Major
BAT
None
CNO1 Contactor
1
Open
Major
BAT
None
CNO2 Contactor
2
Open
Major
BAT
None
CNO3 Contactor
3
Open
Major
BAT
None
COF Queue
Overflow
Warning None None
COR
Number Did Not Respond
Warning
None
None
CPA
Circuit Pack Fail
Major
CTLR
CTLR
CRA Controller
Fail
Major CTLR CTLR
DID Rectifier
ID
Conflict
Major RECT None
EMD
Energy Management Disabled Warning
None
None
EPD
Excess Plant Drain
Minor
RECT
None
EPO
Emergency Power Off
Critical
BATT
None
EPR
External Password Reset
Warning
None
None
ETO
Engine Transfer Timeout
Minor
AC
None
EXL
Excessive Login Attempts
Warning
None
None
FAJ
External Fuse Major
Major
DIST
MJF
FAN
External Fuse Minor
Minor
DIST
MNF
HCL History
Cleared
RO
None None