Usb interface, Wiring alarm outputs, Usb interface wiring alarm outputs – GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 29

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
29
USB Interface
This interface is reserved for future use.
Wiring Alarm Outputs
These external alarms may be wired to customer external office alarms at their
destination.
Form-C Alarm Contact Ratings
60Vdc, 0.3A
Conductor Size for terminating on Alarm
board
18 – 22AWG (if less than 18AWG, use
multi-conductor cable for mechanical
integrity)
Refer to Table 4-B and 4-C for lead designations and their descriptions for leads
terminating on the BSL alarm interface board.