GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 68

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
68
Step Action
NOTE: Verify that the Alarm center has been notified of potential alarms being
generated.
1.
Place System in Float Mode
From the Default Display of the controller, note the system mode of operation:
IF the mode is FLOAT, go to Step 2.
If the mode is NOT Float (ex. – BOOST), place the system in FLOAT
mode before going to Step 2.
2.
Turn all Available Rectifiers On
If rectifiers have been manually turned off, turn them back on. Verify that all
rectifiers are on and sharing load.
3.
Noting the Dip Switch Settings
Dip Switch settings determine if some controller features are enabled or
disabled. If the Millennium II controller is to have the same configurations,
the old settings on SW202 must be noted:
Figure 6-1: Millennium Controller Dip Switch Positions
Record the Switch Positions for future reference –
Basic Controller (BSH) Dip Switch Settings
Switch
Position
Description Switch
Setting
(1 or 0)
SW202-8 Front
Panel
Configuration
SW202-7
Auto Rectifier Restarts
SW202-6
Critical = Major Relays
SW202-5 Alarm
Test
SW202-4
HVSD during Alarm Test
SW202-3 Boost
Mode
SW202-2 External
Timed
Boost
SW202-1
Password Reset for Indep Modem