Wiring alarm and control inputs – GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 32
Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
32
Wiring Alarm and Control Inputs
In a standard Galaxy Power System configuration, plant level alarms are sent to the
controller via the Bay Interface Card through serial data communication. The following
alarm inputs are provided for discretionary use in non-standard applications.
Table 4-C: Controller Alarm and Control Inputs
Alarm Pin
Number
Signal Name
Low Voltage 2 Disconnect State Detect
61
LVD2
Fuse Alarm Major
63
FAJ
Fuse Alarm Minor
65
FAN
Auxiliary Alarm Major
64
AMJ
Auxiliary Alarm Minor
66 AMN
Timer Float Control
67
TFLT
Timer Boost Control
68
TBST
Plant Battery Test
71
PBT
Open String Detect
72
OS
Transfer Rectifier 1
73
TR1
General Purpose Input 4
74
IN-4 previously TEQ
General Purpose Input -5 (Previously
Engine Transfer)
75
IN-5 Previously ETR
Reserve Operation
77
RO
Transfer Rectifier 2
79
TR2
Transfer Rectifier 4
80
TR4
Reserve Battery-Emergency Power Off
81
RBRPO
General Purpose Input 1
82
IN-1
BTP or General Purpose Input 2
83
IN-2/BTP
Low Voltage 1 Disconnect State Detect
84
LVD1
Transfer Rectifier 3
85
TR3
General Purpose 4-20mA Measuring
Circuit
87 4-20mA
General Purpose 4-20mA Measuring
Circuit-RTN
88 4-20mAR
BTPFLT or Generic Input 3
89
IN-3/ BTPFLT
Low Voltage 3 Disconnect State Detect
Also
Battery Thermal Protect Major
90 LVD3/
BTMJ
General Purpose 0-5Vdc Measuring
Circuit
91 0-5V
General Purpose 0-5Vdc Measuring
Circuit-RTN
92 0-5VR