Modbus Memory Map
74
3
6EA9
Function X HRGF Location Contactor Fre-
quency
0.5 to 2
Hz
0.25
F001
100
6EAA
Function X HRGF Location Contactor Duty
Cycle
0 to 100
%
1
F001
50
6EAB
Function X HRGF Location Manual Function
To Start
0 to 4
---
1
F001
0
Function X HRGF Location (Read Only)
6EAC
Function X HRGF Location Manual Availabil-
ity
0 to 15
---
1
F500
0
Function X HRGF Location (Read/Write Setting)
6EAD
Function X HRGF Location Test Contactor
Pulsing
0 to 4
---
1
F001
0
6EAE
Function X HRGF Location Subinterval
20 to 60
s
5
F001
30
Contact Input Configuration (Read/Write Setting) (2 modules)
7003
Board x I/O Direction High
0 to 4294967295
---
1
F737
0
7005
Board x I/O Direction Low
0 to 4294967295
---
1
F736
0
7007
...Repeated for module number 2
Mandatory (Read/Write Setting)
700B
Reserved (2 items)
---
---
---
F001
0
Discrete I/O Configuration (Read Only)
702A
Boards Detected
0 to 8
---
1
F001
0
702B
Boards Used
0 to 8
---
1
F001
0
702C
Total I/O Points Available
0 to 65535
---
1
F001
0
702D
Contact Input Count
0 to 128
---
1
F001
0
702E
Contact Output Count
0 to 128
---
1
F001
0
Discrete I/O Configuration (Read/Write Setting)
702F
Boards Expected
0 to 2
---
1
F001
0
Expanded Digital I/O States (Read Only)
703F
Contact Input x State (128 items)
0 to 1
---
1
F108
0 (Off)
70BF
Contact Output x State (128 items)
0 to 1
---
1
F108
0 (Off)
Contact Inputs (Read/Write Setting) (128 modules)
713F
Contact Input x Name
---
---
---
F200
“Contact Input 1
“
7153
Contact Input x Events
0 to 1
---
1
F102
1 (Enabled)