2 flexlogic operand states, 1 breaker control flex operand states – GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 10
![background image](/manuals/294929/10/background.png)
Integrator’s Guide
10
1.1.2 FlexLogic Operand States
After each protection pass, all the information regarding each operand's state is updated in
corresponding Modbus register. The section
PLC Interface (Read/Write) on page 110
is the
complete list of registers holding state information of corresponding operand.
1.1.2.1 Breaker Control Flex Operand States
Each breaker has 13 different states shown in
Table 1-2
. Each one of them corresponds to a
different bit in the data item.
Table 1-2 Breaker Control status bit field
The breaker states for all 30 breakers span across 25 consecutive modbus registers as shown in
. See
PLC Interface (Read/Write) on page 110
for memory locations.
Table 1-3 Breaker status offsets
Bit
Value
Notes
0
Breaker Opened
1
Breaker Closed
2
Breaker Locked Out
3
Closing Spring Charged
4
Primary Disconnect Connected
5
Primary Disconnect Disconnected
6
Secondary Disconnect Connected
7
Breaker Ready
8
Breaker Available
9
Breaker Open Failed
10
Breaker Close Failed
11
Breaker Fault
12
Breaker RELT State
Not used in this release. It shall be always set to 0.
Breaker Number
Register
Offset
Bit Offset
Notes
Breaker 1
0
0
N/A
Breaker 2
0
13
This breaker’s information spans
over two adjacent registers
Breaker 3
1
10
This breaker’s information spans
over two adjacent registers
Breaker 4
2
7
This breaker’s information spans
over two adjacent registers
...
...
...
...