GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 64
![background image](/manuals/294929/64/background.png)
Modbus Memory Map
64
3
3839
SRC X HRGF Ground Resistance
5 to 500
---
1
F001
5
383A
SRC X HRGF CT Rating
10 to 10
---
1
F001
10
383B
Reserved (8 items)
---
---
---
F001
0
3843
SRC X High Curr Trigger Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
3844
SRC X High Curr Trigger Alarm Pickup Set-
ting
0.1 to 9
---
0.1
F001
20
3845
SRC X High Curr Trigger Alarm Delay Setting
1 to 120
---
1
F001
12
3846
SRC X High Curr Trigger Alarm WFC Enable
0 to 1
---
1
F102
0 (Disabled)
3847
SRC X High Curr Trigger Alarm Max WF
0 to 30
---
1
F001
15
Source Settings (Read Only) (30 modules)
3848
SRC X High Curr Trigger Alarm WF Triggered
0 to 30
---
1
F001
0
Source Settings (Read/Write Command) (30 modules)
3849
SRC X High Curr Trigger Alarm WF Count
Reset
0 to 1
---
1
F126
0 (No)
384A
SRC X Settings Reserved (40 items)
---
---
---
F001
0
3872
...Repeated for module number 2
3926
...Repeated for module number 3
39DA
...Repeated for module number 4
3A8E
...Repeated for module number 5
3B42
...Repeated for module number 6
3BF6
...Repeated for module number 7
3CAA
...Repeated for module number 8
3D5E
...Repeated for module number 9
3E12
...Repeated for module number 10
3EC6
...Repeated for module number 11
3F7A
...Repeated for module number 12
402E
...Repeated for module number 13
4000
...Repeated for module number 14
4196
...Repeated for module number 15
424A
...Repeated for module number 16
42FE
...Repeated for module number 17
43B2
...Repeated for module number 18
4466
...Repeated for module number 19