GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 62
![background image](/manuals/294929/62/background.png)
Modbus Memory Map
62
3
37EB
Source Settings Reserved 2 (7 items)
---
---
---
F001
0
37F2
SRC X PL Trip Enable
0 to 1
---
1
F102
0 (Disabled)
37F3
SRC X PL Trip Pickup Setting
8 to 50
---
1
F001
8
37F4
SRC X PL Trip Time Delay
0.5 to 600
---
0.5
F001
300
37F5
SRC X PL Trip Block Volt Enable
0 to 1
---
1
F102
0 (Disabled)
37F6
SRC X PL Open or Trip Setting
0 to 1
---
1
F727
1 (Trip and acti-
vate lockout)
37F7
SRC X PL Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
37F8
SRC X PL Alarm Pickup Setting
8 to 50
---
1
F001
8
37F9
SRC X PL Alarm Time Delay
0.5 to 600
---
0.5
F001
150
37FA
SRC X PL Alarm Block Volt Enable
0 to 1
---
1
F102
0 (Disabled)
Source Settings (Read Only) (30 modules)
37FB
SRC X PL Trip Voltage Setting
5 to 5
---
1
F001
5
37FC
SRC X PL Alarm Blocking Voltage Setting
5 to 5
---
1
F001
5
Source Settings (Read/Write Setting) (30 modules)
37FD
Source Settings Reserved 3 (3 items)
---
---
---
F001
0
3800
SRC X Rev Power Trip Enable
0 to 1
---
1
F102
0 (Disabled)
3801
SRC X Rev Power Trip Pickup Setting
10 to 990
---
10
F001
990
3802
SRC X Rev Power Trip Time Delay
0.5 to 600
---
0.5
F001
300
3803
SRC X Rev Power Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
3804
SRC X Rev Power Alarm Pickup Setting
10 to 990
---
10
F001
990
3805
SRC X Rev Power Alarm Time Delay
0.5 to 600
---
0.5
F001
150
3806
SRC X Rev Power Trip or Open
0 to 1
---
1
F727
1 (Trip and acti-
vate lockout)
3807
Source Settings Reserved 4 (4 items)
---
---
---
F001
0
380B
SRC X High Curr Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
380C
SRC X High Curr Alarm Pickup Setting
50 to 200
---
5
F001
200
380D
SRC X High Curr Alarm Time Delay
1 to 15
---
1
F001
15
380E
Source Settings Reserved 5 (5 items)
---
---
---
F001
0
3813
SRC X Total Breaker Operations
0 to 65535
---
1
F001
0
3814
SRC X Total Breaker No Load Operations
0 to 65535
---
1
F001
0
3815
SRC X Total Breaker Load Operations
0 to 65535
---
1
F001
0
3816
SRC X Total Breaker Fault Operations
0 to 65535
---
1
F001
0