GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 42
![background image](/manuals/294929/42/background.png)
Modbus Memory Map
42
3
0347
Energy Clear Command
0 to 1
---
1
F126
0 (No)
Fault And Event Test Trigger (Read/Write Command)
0348
Fault Trigger Command
0 to 1
---
1
F126
0 (No)
Demand (Read/Write Setting)
0349
Demand Subinterval Length
1 to 60
---
1
F001
1
034A
Demand Subintervals Per Interval
1 to 15
---
1
F001
1
Demand (Read/Write Command)
034B
Demand Reset All Command
0 to 1
---
1
F126
0 (No)
Demand (Read Only)
034C
Number Of Demand Resets All
0 to 4294963200
---
1
F003
0
034E
Last Demand Reset All DateTime
0 to 4294967295
---
1
F050
0
Demand (Read/Write Command)
0350
Demand Log Clear All Command
0 to 1
---
1
F126
0 (No)
Demand (Read Only)
0351
Demand Log Last Cleared All Date
0 to 4294967295
---
1
F050
0
Waveform Capture (Read Only)
035D
Number WF Records Available
0 to 65535
---
1
F001
0
Waveform Capture (Read/Write Command)
035E
Waveform Clear Command
0 to 1
---
1
F126
0 (No)
Waveform Capture (Read Only)
035F
Waveform Last Clear Date
0 to 4294967295
---
1
F050
0
Waveform Capture (Read/Write Command)
0361
Waveform Trigger Command
0 to 1
---
1
F126
0 (No)
Waveform Capture (Read/Write Setting)
0362
Waveform Trigger Mode
0 to 1
---
1
F118
0 (Automatic
Overwrite)
0363
Waveform Trigger Position
0 to 119
Half
Cycles
1
F001
60
Waveform Capture (Read Only)
0364
Waveforms Since Last Clear
0 to 4294967295
---
1
F003
0
0366
Reserved (2 items)
---
---
---
F001
0
Waveform Capture (Read/Write Setting)