GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 40
Modbus Memory Map
40
3
0036
Reserved
---
---
---
F001
0
Installation (Read/Write Setting)
0080
CPU ID
0 to 1
---
1
F717
0 (CCPU A)
0081
CPU Commissioned
0 to 1
---
1
F102
0 (Disabled)
0082
CPU Name
---
---
---
F200
“UNNAMED”
0096
System Frequency
50 to 60
Hz
10
F001
60
0097
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
Clock (Read/Write Setting)
00E0
RTC Set Time
0 to 4294967295
---
1
F050
0
Clock (Read Only)
00E2
Date Time Changed
0 to 4294967295
---
1
F050
0
Communications (Read/Write Setting)
00EC
External Ethernet IP Address
0 to 4294967295
---
1
F003
3232235876
00EE
External Ethernet IP Subnet Mask
0 to 4294963200
---
1
F003
4294967040
00F0
External Ethernet Gateway IP Address
0 to 4294967295
---
1
F003
0
00F2
Reserved (5 items)
---
---
---
F001
0
Event Recorder (Read Only)
0150
Events Since Last Clear
0 to 4294967295
---
1
F003
0
0152
Number of Available Events
0 to 4294967295
---
1
F003
0
0154
Event Recorder Last Cleared Date
0 to 4294967295
---
1
F050
0
Modbus File Transfer (Read/Write)
0156
Name of file to read
---
---
---
F204
(none)
Modbus File Transfer (Read Only)
017E
Character position of current block within
file
0 to 4294967295
---
1
F003
0
0180
Size of currently-available data block
0 to 65535
---
1
F001
0
0181
Block of data from requested file (122 items)
0 to 65535
---
1
F001
0
Modbus File Transfer Area 2 (Read/Write)
01FB
Name of file to read
---
---
---
F204
(none)
Modbus File Transfer Area 2 (Read Only)
0223
Character position of current block within
file
0 to 4294967295
---
1
F003
0
0225
Size of currently-available data block
0 to 65535
---
1
F001
0