1.1.2.17 Synch Check Flex Operand States

Each relay has 10 different states shown in

Table 1-34

. Each one of them corresponds to a different

bit in the data item.

Table 1-34 Synch Check status bit field

The relay states for all12 relays span across 8 consecutive modbus registers as shown in

Table 1-35

.

See

PLC Interface (Read/Write) on page 110

for memory locations.

Table 1-35 Synch Check status offsets

Bit

Value

0

Dead Source Operated

1

Dead Source Dropout

2

Synch Operated

3

Synch Dropout

4

Close Operated

5

Close Dropout

6

V1 Above Minimum

7

V2 Above Minimum

8

V1 Below Maximum

9

V2 Below Maximum

Zone Number

Register
Offset

Bit Offset

Notes

Relay 1

0

0

Relay 2

0

10

This relay’s information spans
over two adjacent registers

Relay 3

1

4

Relay 4

1

14

This relay’s information spans
over two adjacent registers

Relay 5

2

8

This relay’s information spans
over two adjacent registers

Relay 6

3

2

Relay 7

3

12

Relay 8

4

6

Relay 9

5

0

Relay 10

5

10

Relay 11

6

4

Relay 12

6

14

7

8

Bits from 8 thru 15 are not used
and shall always be set to 0