Modbus Memory Map
66
3
4E3E
...Repeated for module number 13
4E5C
...Repeated for module number 14
4E7A
...Repeated for module number 15
4E98
...Repeated for module number 16
4EB6
...Repeated for module number 17
4ED4
...Repeated for module number 18
4EF2
...Repeated for module number 19
4F10
...Repeated for module number 20
4F2E
...Repeated for module number 21
4F4C
...Repeated for module number 22
4F6A
...Repeated for module number 23
4F88
...Repeated for module number 24
4FA6
...Repeated for module number 25
4FC4
...Repeated for module number 26
4FE2
...Repeated for module number 27
5000
...Repeated for module number 28
501E
...Repeated for module number 29
503C
...Repeated for module number 30
Synch Check Settings (Read/Write Setting) (12 modules)
505A
Synch Check Enable
0 to 1
---
1
F102
0 (Disabled)
505B
Synch Check V1 Source
0 to 29
---
1
F001
0
505C
Synch Check V2 Source
0 to 29
---
1
F001
0
505D
Synch Check Max Volt Diff
0 to 90
---
0.5
F001
0
505E
Synch Check Max Phase Diff
0 to 60
---
1
F001
0
505F
Synch Check Max Freq Diff
0 to 2
---
0.1
F001
0
5060
Synch Check Dead Max V1
5 to 50
---
1
F001
5
5061
Synch Check Live Min V1
50 to 100
---
1
F001
50
5062
Synch Check Dead MaxV2
5 to 50
---
1
F001
5
5063
Synch Check Live Min V2
50 to 100
---
1
F001
50
5064
Reserved (4 items)
---
---
---
F001
0
5068
Synch Check Dead Source Select
0 to 5
---
1
F176
0 (None)
Synch Check Settings (Read Only) (12 modules)
5069
Synch Check Status
0 to 65535
---
1
F001