[6] VIRTUAL OUTPUTS (1-64)
[10] CONTACT OUTPUTS VOLTAGE DETECTED ( 1-64)
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1-64)
[12] CONTACT OUTPUTS CURRENT DETECTED (1-64)
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1-64)
[14] REMOTE INPUTS (1-32)
[28] INSERT (Via Keypad only)
[32]
END
[34] NOT (1 INPUT)
[36] 2 INPUT XOR (0)
[38] LATCH SET/RESET (2 INPUTS)
[40] OR (2-16 INPUTS)
[42] AND (2-16 INPUTS)
[44] NOR (2-16 INPUTS)
[46] NAND (2-16 INPUTS)
[48] TIMER (1-32)
[50] ASSIGN VIRTUAL OUTPUT (1 - 64)
[52] SELF-TEST ERROR (See F141 for range)
[56] ACTIVE SETTING GROUP (1-8)
[62] MISCELLANEOUS EVENTS (See F146 for range)
[64-127] ELEMENT STATES (Refer to Memory Map Element States Section)
F500
UINT16
PACKED BITFIELD
First register indicates I/O state with bits 0(MSB)-15(LSB) corresponding to I/0 state 1-16.
Second register indicates I/O state with bits 0-15 corresponding to I/0 state 17-32 (if
required). Third register indicates I/O state with bits 0-15 corresponding to I/0 state 33-
48 (if required). Fourth register indicates I/O state with bits 0-15 corresponding to I/0
state 49-64 (if required). The number of registers required is determined by the specific
data item.
A bit value of 0 = Off, 1 = On
F701
BITFIELD
SRCx Node Internal Diagnostics Bit Mask
0
Power-on Self Test Error Detected
1
Built-In-Test Error Detected
2
Invalid Data Detected
3
Jamb sync occurred over threshold
4
Invalid node configuration detected