63
3
3817
SRC X Breaker Percent Load Life
0 to 655.35
---
0.01
F001
0
Source Settings (Read Only) (30 modules)
3818
SRC X Percent Mechanical Life
0 to 655.35
---
0.01
F001
0
Source Settings (Read/Write Setting) (30 modules)
3819
SRC X Time Date Last Breaker Operation
0 to 4294967295
---
1
F050
0
381B
SRC X Time Date Initial Energization
0 to 4294967295
---
1
F050
0
Source Settings (Read Only) (30 modules)
381D
SRC X Breaker Service Hours
0 to 4294967295
---
1
F003
0
Source Settings (Read/Write Setting) (30 modules)
381F
Source Settings Reserved 6 (5 items)
---
---
---
F001
0
3824
SRC X UF Trip Enable
0 to 1
---
1
F102
0 (Disabled)
3825
SRC X UF Trip Pickup Setting
45 to 60
---
0.1
F001
450
3826
SRC X UF Trip Time Delay
0.1 to 600
---
0.1
F001
300
3827
SRC X UF Trip Blocking Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
3828
SRC X UF Trip or Open setting
0 to 1
---
1
F727
1 (Trip and acti-
vate lockout)
3829
SRC X UF Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
382A
SRC X UF Alarm Pickup Setting
45 to 60
---
0.1
F001
450
382B
SRC X UF Alarm Time Delay
0.1 to 600
---
0.1
F001
150
382C
SRC X UF Alarm Blocking Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
382D
SRC X OF Trip Enable
0 to 1
---
1
F102
0 (Disabled)
382E
SRC X OF Trip Pickup Setting
50 to 70
---
0.1
F001
500
382F
SRC X OF Trip Time Delay
0.1 to 600
---
0.1
F001
300
3830
SRC X OF Trip Blocking Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
3831
SRC X OF Trip or Open setting
0 to 1
---
1
F727
1 (Trip and acti-
vate lockout)
3832
SRC X OF Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
3833
SRC X OF Alarm Pickup Setting
50 to 70
---
0.1
F001
500
3834
SRC X OF Alarm Time Delay
0.1 to 600
---
0.1
F001
150
3835
SRC X OF Alarm Blocking Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
3836
SRC X HRGF Enable
0 to 1
---
1
F102
0 (Disabled)
3837
SRC X HRGF Pickup
0.1 to 10
---
0.1
F001
20
3838
SRC X HRGF Delay
0.5 to 5
---
0.1
F001
5