GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 43
43
3
0368
Waveform Trigger Thru FlexLogic
0 to 65535
---
1
F300
0
Preventive Maintenance (Read/Write Setting)
0370
Load Life Rating 800A
0 to 65535
---
1
F001
2800
0371
Load Life Rating 1600A
0 to 65535
---
1
F001
1200
0372
Load Life Rating 2000A
0 to 65535
---
1
F001
1000
0373
Load Life Rating 3200A
0 to 65535
---
1
F001
600
0374
Load Life Rating 4000A
0 to 65535
---
1
F001
500
0375
Load Life Rating 5000A
0 to 65535
---
1
F001
400
0376
Mechanical Life Rating 800A
0 to 65535
---
1
F001
12500
0377
Mechanical Life Rating 1600A
0 to 65535
---
1
F001
4000
0378
Mechanical Life Rating 2000A
0 to 65535
---
1
F001
4000
0379
Mechanical Life Rating 3200A
0 to 65535
---
1
F001
1500
037A
Mechanical Life Rating 4000A
0 to 65535
---
1
F001
1500
037B
Mechanical Life Rating 5000A
0 to 65535
---
1
F001
1500
037C
Load Life Max Current 800A
1 to 50
---
1
F001
15
037D
Load Life Max Current 1600A
1 to 50
---
1
F001
15
037E
Load Life Max Current 2000A
1 to 50
---
1
F001
15
037F
Load Life Max Current 3200A
1 to 50
---
1
F001
13
0380
Load Life Max Current 4000A
1 to 50
---
1
F001
9
0381
Load Life Max Current 5000A
1 to 50
---
1
F001
7
Hardware Information (Read Only)
03A0
Flash Lifetime
1 to 10
---
1
F001
1
Source Vectors (Read/Write Setting)
0408
Reserved (2 items)
---
---
---
F001
0
040A
Expected Nodes X State
0 to 4294967295
---
1
F722
0
040C
Source Node Identifier LED X State
0 to 4294967295
---
1
F722
0
040E
Node Setting Changed X State
0 to 4294967295
---
1
F722
0
Source Vectors (Read Only)
0410
Nodes Communicating X State
0 to 4294967295
---
1
F722
0
0412
Nodes Commissioned X State
0 to 4294967295
---
1
F722
0
0414
Duplicate Nodes X State
0 to 4294967295
---
1
F722
0
0416
Node Internal Diagnostics X State
0 to 4294967295
---
1
F722
0
0418
Node System Diagnostics X State
0 to 4294967295
---
1
F722
0