GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 61
![background image](/manuals/294929/61/background.png)
61
3
37BF
SRC X PT Source Node Identifier
0 to 29
---
1
F001
0
Source Settings (Read/Write Setting) (30 modules)
37C0
SRC X Breaker Connection
0 to 1
---
1
F712
0 (Forward)
37C1
Reserved (2 items)
---
---
---
F001
0
37C3
Source Settings Reserved (15 items)
---
---
---
F001
0
37D2
SRC X PT Rating
0 to 6
---
1
F719
0 (None)
37D3
SRC X UV Trip Enable
0 to 1
---
1
F102
0 (Disabled)
37D4
SRC X UV Trip Curve Type
0 to 1
---
1
F726
1 (Constant time
curve)
37D5
SRC X UV Trip Pickup Setting
10 to 95
---
1
F001
50
37D6
SRC X UV Trip Time Delay
0.5 to 600
---
0.5
F001
300
37D7
SRC X UV Trip Phase Requirement
1 to 3
---
1
F001
1
37D8
SRC X UV Trip Block Volt Enable
0 to 1
---
1
F102
0 (Disabled)
37D9
SRC X UV Trip Block Volt Setting
5 to 75
---
1
F001
5
37DA
SRC X UV Trip Open or Trip Setting
0 to 1
---
1
F727
1 (Trip and acti-
vate lockout)
37DB
SRC X UV Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
37DC
SRC X UV Alarm Curve Type
0 to 1
---
1
F726
1 (Constant time
curve)
37DD
SRC X UV Alarm Pickup Setting
10 to 95
---
1
F001
50
37DE
SRC X UV Alarm Time Delay
0.5 to 600
---
0.5
F001
150
37DF
SRC X UV Alarm Phase Requirement
1 to 3
---
1
F001
1
37E0
SRC X UV Alarm Block Volt Enable
0 to 1
---
1
F102
0 (Disabled)
37E1
SRC X UV Alarm Block Volt Setting
5 to 75
---
1
F001
5
37E2
SRC X OV Trip Enable
0 to 1
---
1
F102
0 (Disabled)
37E3
SRC X OV Trip Pickup Setting
105 to 125
---
1
F001
120
37E4
SRC X OV Trip Time Delay
0.5 to 600
---
0.5
F001
300
37E5
SRC X OV Trip Phase Requirement
1 to 3
---
1
F001
1
37E6
SRC X OV Trip Open or Trip Setting
0 to 1
---
1
F727
1 (Trip and acti-
vate lockout)
37E7
SRC X OV Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
37E8
SRC X OV Alarm Pickup Threshold
105 to 125
---
1
F001
120
37E9
SRC X OV Alarm Time Delay
0.5 to 600
---
0.5
F001
150
37EA
SRC X OV Alarm Phase Requirement
1 to 3
---
1
F001
1