Modbus memory map, 3 modbus memory map – GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 39
39
3
3
Modbus Memory Map
NOTE: A multiplier factor may be necessary in cases where an integer value is returned but the
Range and/or Step imply a greater precision. In these cases, it is necessary to divide the
returned value by 10 for a step of “0.1” or “0.5”; by 100 for a step of “.01”; and so on. Similarly, it is
necessary to multiply by these factors prior to writing a settings value. This note does not apply
to any step value greater than 1 (a step of “10” does not require a multiplier, for example). This
note also does not apply to values returned in floating point format. See the format codes at the
end of the map for more information.
NOTE: Discrete I/O output state registers (Contact Output x State - register range from x9180
to x91FF and Contact Output States - register range from xB256 to 0xB25D) contain correct
information only when FlexLogic Active register (x0034) contains value 1 (yes).
Addr
Register Name
Range
Units
Step
For-
mat
Factory Default
Product Information (Read Only)
0000
FBW Product Type
0 to 2
---
1
F716
0 (Low Voltage
Switchgear)
0001
Serial Number
---
---
---
F203
“0”
0009
External Ethernet MAC Address
---
---
---
F072
0
000C
Reserved (3 items)
---
---
---
F001
0
000F
CPU Hardware Version
0 to 655.35
---
0.01
F001
100
0010
CPU Firmware Version
0 to 655.35
---
0.01
F001
100
0011
CPU Firmware Boot Code Version
0 to 655.35
---
0.01
F001
100
0012
Build Date
---
---
---
F200
“0”
0026
Synchronizer Board Status
0 to 1
---
1
F102
0 (Disabled)
0027
Synchronizer Board Frequency Setting
50 to 60
Hz
10
F001
60
0028
Last Energy Clear Date
0 to 4294967295
---
1
F050
0
002A
Last CPU Commissioned Date
0 to 4294967295
---
1
F050
0
002C
Expected Node Protocol Version
0 to 655.35
---
0.01
F001
0
002D
Summary Number
---
---
---
F205
“0”
0033
Line Up
0 to 99
---
1
F001
1
0034
System Frequency Detected
0 to 65535
Hz
1
F001
0
0035
CPU Modbus Map Version
0 to 655.35
---
0.01
F001
450