GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 111
111
3
DCC6
Reserved (12 items)
---
---
---
F001
0
DCD2
ST Overcurrent Flex Operand States (6 items)
0 to 65535
---
1
F500
0
DCD8
Summation MSGF Zone Flex Operand States
0 to 65535
---
1
F500
0
DCD9
Synch Check Flex Operand States (8 items)
0 to 65535
---
1
F500
0
DCE1
Under Frequency Flex Operand States (12
items)
0 to 65535
---
1
F500
0
DCED
Under Voltage Flex Operand States (12
items)
0 to 65535
---
1
F500
0
DCF9
Reserved (7 items)
---
---
---
F001
0
Source Setting Groups (Read/Write Setting) (30 modules)
E1FF
SRC X IOC Enabled (16 items)
0 to 1
---
1
F718
1 (Enabled)
E20F
SRC X IOC Pickup Setting Multiplier (16 items)
1.5 to 15
---
0.5
F001
60
E21F
SRC X Short Time Protection Switch (16
items)
0 to 1
---
1
F102
1 (Enabled)
E22F
SRC X Short Time Pickup Setting (16 items)
1.5 to 9
---
0.5
F001
40
E23F
SRC X Short Time I2T Curve (16 items)
0 to 1
---
1
F102
0 (Disabled)
E24F
SRC X Short Time Delay Band Setting (16
items)
0 to 6
---
1
F713
2 (BAND 3)
E25F
SRC X Long Time Delay Band Setting (16
items)
0 to 3
---
1
F711
1 (BAND 2)
E26F
SRC X GF Protection Switch (16 items)
0 to 1
---
1
F102
0 (Disabled)
E27F
SRC X GF Protection Trip Pickup Setting (16
items)
0.2 to 0.6
---
0.01
F001
24
E28F
SRC X GF Protection Trip I2T Curve (16 items)
0 to 1
---
1
F102
1 (Enabled)
E29F
SRC X GF Protection Trip Delay Band Setting
(16 items)
0 to 6
---
1
F713
2 (BAND 3)
E2AF
SRC X GF Protection Trip Priority (16 items)
0 to 30
---
1
F001
0
E2BF
SRC X GF Protection Alarm Enable (16 items)
0 to 1
---
1
F102
0 (Disabled)
E2CF
SRC X GF Protection Alarm Pickup Setting
(16 items)
0.2 to 0.6
---
0.01
F001
24
E2DF
SRC X GF Protection Alarm I2T Curve (16
items)
0 to 1
---
1
F102
1 (Enabled)
E2EF
SRC X GF Protection Alarm Delay Band Set-
ting (16 items)
0 to 6
---
1
F713
2 (BAND 3)
E2FF
...Repeated for module number 2