GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual
Page 71
71
3
68D4
Zone X BD Alarm Pickup Setting (16 items)
100 to 22000
---
100
F001
1200
68E4
Zone X BD Trip Pickup Setting2 (16 items)
100 to 22000
---
100
F001
1200
68F4
Zone X BD Alarm Pickup Setting2 (16 items)
100 to 22000
---
100
F001
1200
6904
Zone X BD Trip Delay Band Setting (16 items)
0 to 6
---
1
F735
2 (BAND 3)
6914
Zone X BD Alarm Delay Band Setting (16
items)
0 to 6
---
1
F735
2 (BAND 3)
6924
Zone X BD Trip Delay Band Setting2 (16
items)
0 to 6
---
1
F735
2 (BAND 3)
6934
Zone X BD Alarm Delay Band Setting2 (16
items)
0 to 6
---
1
F735
2 (BAND 3)
6944
Zone X BD Trip Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
6954
Zone X BD Alarm Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
6964
Zone X BD Backup Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
6974
Zone X BD Backup Time Delta Enabled (16
items)
0 to 1
---
1
F102
0 (Disabled)
6984
Zone X BD Trip or Open
0 to 1
---
1
F727
0 (Open and
don't activate
lockout)
6985
Zone X BD Reserved (16 items)
---
---
---
F001
0
6995
...Repeated for module number 2
6A66
...Repeated for module number 3
6B37
...Repeated for module number 4
Zone X Summation Settings (Read/Write Setting) (2 modules)
6C08
Zone X Summation MSGF Trip Delay Band
Setting (16 items)
0 to 6
---
1
F735
2 (BAND 3)
6C18
Zone X Summation MSGF Alarm Delay Band
Setting (16 items)
0 to 6
---
1
F735
2 (BAND 3)
6C28
Zone X Summation MSGF Trip I2T (16 items)
0 to 1
---
1
F102
0 (Disabled)
6C38
Zone X Summation MSGF Alarm I2T Curve
(16 items)
0 to 1
---
1
F102
0 (Disabled)
6C48
Zone X Summation MSGF Trip Enabled (16
items)
0 to 1
---
1
F102
0 (Disabled)
6C58
Zone X Summation MSGF Alarm Enabled (16
items)
0 to 1
---
1
F102
0 (Disabled)
6C68
Zone X Summation MSGF Trip Pickup Setting
(16 items)
30 to 1200
---
10
F001
1200