4 alarm word and warning word – GE Industrial Solutions AF-650 GP DeviceNet User Manual
Page 55

8.1.4 Alarm Word and Warning Word
Alarm word and Warning word are shown on the display in Hex format. If there is more than one warning or alarm, a sum of all warnings or alarms will be shown.
Alarm word and warning word can also be displayed using the field bus in par. DR-05 Main Actual Value [%].
AF-650 GP or AF-600 FP
Bit (Hex)
Alarm word
(par. DR-90 Alarm Word)
Alarm no.
Major /
minor alarm
Recoverable /
unrecoverable alarm
00000001
Unused
-
-
-
00000002
Drive over temperature
29
Major
Recoverable
00000004
Earth fault
14
Major
Unrecoverable
00000008
Unused
-
-
-
00000010
Control word timeout
18
Minor
Recoverable
00000020
Over current
13
Major
Unrecoverable
00000040
Torque limit
12
Major
Recoverable
00000080
Motor thermistor over temp.
11
Major
Recoverable
00000100
Motor Thermal Electronic Overload
over temperature
10
Major
Recoverable
00000200
Drive overloaded
9
Major
Recoverable
00000400
DC link under voltage
8
Major
Recoverable
00000800
DC link over voltage
7
Major
Recoverable
00001000
Short circuit
16
Major
Unrecoverable
00002000
Inrush fault
33
Major
Recoverable
00004000
Mains phase loss
4
Major
Unrecoverable
00008000
Auto Tune not OK
50
Major
Recoverable
00010000
Live zero error
2
Major
Recoverable
00020000
Internal fault
38
Major
Unrecoverable
00040000
Brake resistor power limit
26
Major
Unrecoverable
00080000
Motor phase U is missing
30
Major
Unrecoverable
00100000
Motor phase V is missing
31
Major
Unrecoverable
00200000
Motor phase W is missing
32
Major
Unrecoverable
00400000
Fieldbus comm. fault
34
Major
Recoverable
00800000
24 V supply fault
47
Major
Unrecoverable
01000000
Mains failure
36
Major
Recoverable
02000000
1.8 V supply fault
48
Major
Unrecoverable
04000000
Brake resistor short circuit
25
Major
Recoverable
08000000
Brake chopper fault
27
Major
Recoverable
10000000
Unused
-
-
-
20000000
Unused
-
-
-
40000000
Unused
-
-
-
80000000
Unused
-
-
-
AF-600FP /650 GP DeviceNet Operating Instructions
54
8