8 Troubleshooting
8.1 Troubleshooting
8.1.1 LED Status
First, check the LEDs.
The DeviceNet control card contains two bi-colour (green/red) LEDs to indicate the state of the device and the network respectively.
The upper LED indicates module status (MS). The lower LED indicates network
status (NS).
State
Bi-colour LED
Status
No Power
Off
There is no power applied to the option
Device operational
Green
The DeviceNet option is operating in normal condition.
Standby
Green
The DeviceNet option needs commissioning due to con-
figuration missing, incomplete or incorrect.
Minor fault
Red
Recoverable fault.
Unrecoverable fault Red
Unrecoverable fault, may need replacing.
Self test
Green
The DeviceNet option is in Self-test mode.
Red
Table 8.1: LED: Module Status (MS)
State
Bi-colour LED
Status
No Power/Not on-
line
Off
The option has not completed “Duplicate MAC ID” test yet
or may not be powered.
On-line, not connec-
ted
Green
The option is on-line, but not allocated to a master.
On-line and connec-
ted
Green
The DeviceNet option is on-line and connected to a mas-
ter.
Connection time-out Red
One or more I/O connections are in time-out state.
Critical link failure
Red
Table 8.2: LED: Network Status (NS)