3 How to Configure the System
3.1 Configure the DeviceNet Network
All DeviceNet stations that are connected to the same network must have a
unique station address. The DeviceNet address of the frequency converter
can be selected via:
-
Hardware switches (default 63)
-
par. DN-02 MAC ID (default 63)
-
Class code 0X03, Instance 1, Attribute 1
3.1.1 Setting the DeviceNet Address using the Hardware Switches
Setting the DeviceNet Address using the Hardware Switches: Using the hardware switches it is possible to select an address range from 0-63 (factory setting 63)
according to the table below:
Switch
8
7
6
5
4
3
2
1
Address value
-
-
+32
+16
+8
+4
+2
+1
Ex. address 5
-
-
OFF
OFF
OFF
ON
OFF
ON
Ex. address 20
-
-
OFF
ON
OFF
ON
OFF
OFF
Ex. address 35
-
-
ON
OFF
OFF
OFF
ON
ON
NB!
Switch off the power supply before changing the hardware switches.
The address change will come into effect at the next power-up, and can be read in par. DN-02 MAC ID.
3.1.2 Setting the DeviceNet Address via par. DN-02 MAC ID
The address can be set via par. DN-02 MAC ID if the hardware switches are set to 63 (factory setting). The address change will come into effect at the next power-
up.
3.1.3 Setting the DeviceNet Address with the Object Class Code 0x03, Attribute 1, Instance 1
The address can be set via the DeviceNet object class code 0x03 attribute 1 command if the hardware switch is set to 63 (factory setting). A new address becomes
effective immediately after the class code 0x03, Instance 1, Attribute 1 command.
AF-600FP /650 GP DeviceNet Operating Instructions
11
3