GE Industrial Solutions AF-650 GP DeviceNet User Manual
Page 40

NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital input) and/or via the network.
Option:
Function:
[0]
Digital Input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals (digital input) and/or via the network.
[0]
Digit Input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-53 Start Select
Option:
Function:
Select control of the frequency converter start function via the terminals (digital input) and/or via the
network.
[0]
Digit Input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial communication port or network option module.
[2]
Logic AND
Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.
[3] *
Logic OR
Activates Start command via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-54 Reversing Select
Option:
Function:
[0]
Digital Input
Select control of the frequency converter reverse function via the terminals (digital input) and/or via the
network.
[1]
Bus
Activates the Reverse command via the serial communication port or network option module.
[2]
Logic AND
Activates the Reverse command via the network/serial communication port, AND additionally via one of
the digital inputs.
[3] *
Logic OR
Activates the Reverse command via the network/serial communication port OR via one of the digital
inputs.