8.2.8 Extended Diagnostics
Using the extended diagnostics function, alarm and warning information can be received from the frequency converter. The setting of par. O-07 Diagnosis
Trigger determines which frequency converter events should trigger the extended diagnostics function.
When par. O-07 Diagnosis Trigger is set to Disable [0], no extended diagnostics data are sent regardless of whether they appear in the frequency converter.
When par. O-07 Diagnosis Trigger is set to Alarms [1], extended diagnostics data are sent when one or more alarms arrive in the alarm par. DR-90 Alarm Word
or par. PB-53 Profibus Warning Word.
When par. O-06 Reset Control Word Timeout is set to Alarms/Warnings [2], extended diagnostics data are sent if one or more alarms/warnings arrive in the alarm
par. DR-90 Alarm Word or par. PB-53 Profibus Warning Word, or in the warning par. DR-92 Warning Word.
The extended diagnostics sequence is as follows: If an alarm or warning appears, the frequency converter will indicate that to the master by sending a high priority
message via the output data telegram. This will cause the master to send a request for extended diagnostics information to the frequency converter, to which
the frequency converter will reply. When the alarm or warning disappears, the frequency converter will again indicate that to the master, and on the following
request from the master, return a standard DP diagnostics frame (6 bytes).
The content of the extended diagnostics frame is as follows:
Byte
Bit no.
Name
0 to 5
Standard DP Diagnostics data
6
PDU length
7
0-7
Status type =0x81
8
8-15
Slot = 0
9
16-23
Status Information
10
24-31
par. DR-90 Alarm Word
11
32-39
par. DR-90 Alarm Word
12
40-47
par. DR-90 Alarm Word
13
48-55
par. DR-90 Alarm Word
14
56-63
Reserved for future use
15
64-71
Reserved for future use
16
72-79
Reserved for future use
17
80-87
Reserved for future use
18
88-95
par. DR-92 Warning Word
19
96-103
par. DR-92 Warning Word
20
104-111
par. DR-92 Warning Word
21
112-119
par. DR-92 Warning Word
22
120-127
Reserved for future use
23
128-135
Reserved for future use
24
136-143
Reserved for future use
25
144-151
Reserved for future use
26
152-159
par. PB-53 Profibus Warning Word
27
160-167
par. PB-53 Profibus Warning Word
28
168-175
Reserved for future use
29
176-183
Reserved for future use
30
184-191
Reserved for future use
31
192-199
Reserved for future use
AF-650 GP/AF-600 FP Profibus DP Operating Instructions