GE Industrial Solutions AF-600 FP Profibus DP User Manual
Page 78

If Logic OR [3] is selected, activation of one signal will activate the function.
Logic OR [3]
Terminal
Bit 02/03/04
Function
0
0
Coast/DC brake/Q-Stop
0
1
Coast/DC brake/Q-Stop
1
0
Coast/DC brake/Q-Stop
1
1
No Coast/DC brake/Q-Stop
The effect of control mode upon the function of par. O-53 Start Select and par. O-54 Reversing Select:
If Digital input [0] is selected, the terminals will control the start and reversing
functions
Digital input [0]
Terminal
Bit 06/15
Function
0
0
Stop/Anti-clockwise
0
1
Stop/Anti-clockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
If Serial communication [1] is selected, commands will be activated only when
given via serial communication.
Serial communication [1]
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Start/Clockwise
1
0
Stop/Anti-clockwise
1
1
Start/Clockwise
If Logic AND [2] is selected, both signals must be activated to perform the
function.
Logic AND [2]
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Stop/Anti-clockwise
1
0
Stop/Anti-clockwise
1
1
Start/Clockwise
If Logic OR [3] is selected, activation of one signal will activate the function.
Logic OR [3]
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Start/Clockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
The effect of control mode upon the function of par. O-55 Set-up Select and par. O-56 Preset Reference Select:
If Digital input [0] is selected, the terminals will control the set-up and preset
reference functions.
Digital input [0]
Terminal
Bit 00/01, 13/14
Function
Msb
Lsb
Msb
Lsb
Preset ref., Set-up no.
0
0
0
0
1
0
0
0
1
1
0
0
1
0
1
0
0
1
1
1
0
1
0
0
2
0
1
0
1
2
0
1
1
0
2
0
1
1
1
2
1
0
0
0
3
1
0
0
1
3
1
0
1
0
3
1
0
1
1
3
1
1
0
0
4
1
1
0
1
4
1
1
1
0
4
1
1
1
1
4
AF-650 GP/AF-600 FP Profibus DP Operating Instructions
77
8