Par. o-10 control word profile, In par. o-50 coasting select, Par. o-05 end-of-timeout function – GE Industrial Solutions AF-600 FP Profibus DP User Manual
Page 57

defines whether to resume the set-up used before the time-out or to retain the set-up endorsed by the
time-out function.
[8]
Select setup 2
See [7] Select setup 1
[9]
Select setup 3
See [7] Select setup 1
[10]
Select setup 4
See [7] Select setup 1
NB!
The following configuration is required in order to change the set-up after a time-out:
Set par. K-10 Active Set-up to [9] Multi set-up and select the relevant link in par. K-12 This Set-up Linked to.
O-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].
[0]
Hold set-up
Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until par.
O-06 Reset Control Word Timeout toggles. Then the frequency converter resumes its original set-up.
[1] *
Resume set-up
Resumes the set-up active prior to the time-out.
O-06 Reset Control Word Timeout
This parameter is active only when Hold set-up [0] has been selected in par. O-05 End-of-Timeout Function.
Option:
Function:
[0] *
Do not reset
Retains the set-up specified in par. O-04 Control Word Timeout Function, following a control word time-
out.
[1]
Do reset
Returns the frequency converter to the original set-up following a control word time-out. The frequency
converter performs the reset and then immediately reverts to the Do not reset [0] setting
O-10 Control Word Profile
Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the fieldbus installed in slot A will
be visible in the Keypad display.
For guidelines in selection of GE Drive profile [0] and PROFIdrive profile [1] please refer to the Serial communication via RS 485 Interface section.
For additional guidelines in the selection of PROFIdrive profile [1], ODVA [5] and CANopen DSP 402 [7], please refer to the Operating Instructions for the installed
fieldbus.
Option:
Function:
[0] *
Drive Profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
O-50 Coasting Select
Option:
Function:
Select control of the coasting function via the terminals (digital input) and/or via the network.
[0]
Digit Input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
AF-650 GP/AF-600 FP Profibus DP Operating Instructions
56