8.2.5 Alarm and Warning Words
Alarm word, Warning word and PROFIBUS warning word are shown on the display in Hex format. If there is more than one warning or alarm, a sum of all warnings
or alarms will be shown. Alarm word, warning word and PROFIBUS warning word can also be displayed using the serial network in par. DR-90 Alarm Word, par.
DR-92 Warning Word and par. PB-53 Profibus Warning Word.
AF-650 GP & AF-600 FP
Bit (Hex)
Unit diag-
nose bit
Alarm word (par.
DR-90 Alarm Word)
Alarm no.
00000001
48
Brake check
28
00000002
49
Power card over temper-
ature
29
00000004
50
Earth fault
14
00000008
51
Control card over tem-
perature
65
00000010
52
Control word timeout
18
00000020
53
Over current
13
00000040
54
Torque limit
12
00000080
55
Motor thermistor over
temp.
11
00000100
40
Motor Electronic Over-
load over temperature
10
00000200
41
Drive overloaded
9
00000400
42
DC link under voltage
8
00000800
43
DC link over voltage
7
00001000
44
Short circuit
16
00002000
45
Inrush fault
33
00004000
46
Mains phase loss
4
00008000
47
Auto Tune not OK
50
00010000
32
Live zero error
2
00020000
33
Internal fault
38
00040000
34
Brake overload
26
00080000
35
Motor phase U is missing
30
00100000
36
Motor phase V is missing
31
00200000
37
Motor phase W is missing
32
00400000
38
Network comm. fault
34
00800000
39
24 V supply fault
47
01000000
24
Mains failure
36
02000000
25
1.8 V supply fault
48
04000000
26
Brake resistor short cir-
cuit
25
08000000
27
Brake chopper fault
27
10000000
28
Option change
67
20000000
29
Drive Initialized
80
40000000
30
Safe stop
68
80000000
31
Mechanical brake low
63
AF-650 GP & AF-600 FP
Bit (Hex)
Unit diag-
nose bit
Warning word (par.
DR-92 Warning Word)
Alarm no.
00000001
112
Brake check
28
00000002
113
Power card over temper-
ature
29
00000004
114
Earth fault
14
00000008
115
Control card
65
00000010
116
Control word timeout
18
00000020
117
Over current
13
00000040
118
Torque limit
12
00000080
119
Motor thermistor over
temp.
11
00000100
104
Motor Electronic Overload
over temperature
10
00000200
105
Drive overloaded
9
00000400
106
DC link under voltage
8
00000800
107
DC link over voltage
7
00001000
108
DC link voltage low
6
00002000
109
DC link voltage high
5
00004000
110
Mains phase loss
4
00008000
111
No motor
3
00010000
96
Live zero error
2
00020000
97
10 V low
1
00040000
98
Brake overload
26
00080000
99
Brake resistor short circuit
25
00100000
100
Brake chopper fault
27
00200000
101
Speed limit
49
00400000
102
Network comm. fault
34
00800000
103
24 V supply fault
47
01000000
88
Mains failure
36
02000000
89
Current limit
59
04000000
90
Low temperature
66
08000000
91
Voltage limit
64
10000000
92
Encoder loss
61
20000000
93
Output frequency limit
62
40000000
94
Unused
-
80000000
95
Warning word 2 (ext. stat.
word)
-
AF-650 GP & AF-600 FP
Bit (Hex)
Unit diag-
nose bit
PROFIBUS warning word (par. PB-53 Pro-
fibus Warning Word)
00000001
160
Connection with DP-master is not ok
00000002
161
Unused
00000004
162
NDL (Network Data link Layer) is not ok
00000008
163
Clear data command received
00000010
164
Actual value is not updated
00000020
165
Baudrate search
00000040
166
PROFIBUS ASIC is not transmitting
00000080
167
Initialising of PROFIBUS is not ok
00000100
152
Drive is tripped
00000200
153
Internal CAN error
00000400
154
Wrong configuration data from PLC
00000800
155
Wrong ID sent by PLC
00001000
156
Internal error occurred
00002000
157
Not configured
00004000
158
Timeout active
00008000
159
Warning 34 active