6 warning and alarm messages, 7 fault messages via dp diagnostics – GE Industrial Solutions AF-600 FP Profibus DP User Manual
Page 81

AF-650 GP & AF-600 FP
Bit (Hex)
Comm. option STW (par. DR-84 Comm. Option STW)
00000001
parameters ok
00000002
configuration ok
00000004
clearmode active
00000008
baudrate search
00000010
waiting for parameterization
00000020
waiting for configuration
00000040
in data exchange
00000080
not used
00000100
not used
00000200
not used
00000400
not used
00000800
MCL2/1 connected
00001000
MCL2/2 connected
00002000
MCL2/3 connected
00004000
data transport active
00008000
not used
NB!
par. DR-84 Comm. Option STW is not part of extended diagnostics.
8.2.6 Warning and Alarm Messages
There is a clear distinction between alarms and warnings. When there is an alarm, the frequency converter will enter a fault condition. After the cause for the
alarm has been cleared, the master will have to acknowledge the alarm message before the frequency converter can start operating again. A warning, on the
other hand, may come when a warning condition appears, then disappear when conditions return to normal, without interfering with the process.
Warnings
Warnings within the frequency converter are represented by a single bit within a warning word. A warning word is always an active parameter. Bit status FALSE
[0] means no warning, while bit status TRUE [1] means warning. Any bit change in the warning word will be notified by a change of bit 7 in the status word.
Alarms
Following an alarm message the frequency converter will enter Fault condition. Only after the fault has been alleviated and the master has acknowledged the
alarm message by setting bit 7 in the control word, will the frequency converter resume operation. Alarms within the frequency converter are represented by a
single bit within an alarm word. An alarm word is always an action parameter. Bit status FALSE [0] means no fault, while bit status TRUE [1] means fault.
8.2.7 Fault Messages via DP Diagnostics
The standard DP function features an on-line diagnostics, which is active during DP initialization as well as data exchange mode.