Bit 08, Speed
≠ reference / Speed = reference
When bit 08 = "0", the current speed of the motor deviates from the set speed reference value. This may occur, for example, when the speed is being changed
during start/stop through ramp up/down.
When bit 08 = "1", the current speed of the motor corresponds to the set speed reference value.
Bit 09, Local operation/Bus control
Bit 09 = "0" indicates that the frequency converter has been stopped by means of the stop button on the control panel, or that [Linked to hand] or [Local] has been
selected in par. F-02 Operation Method.
When bit 09 = "1", the frequency converter can be controlled through the serial interface.
Bit 10, Out of frequency limit/Frequency limit OK
When bit 10 = "0", the output frequency is outside the limits set in par. H-72 Warning Speed Low and par. H-73 Warning Speed High. When bit 10 = "1", the output
frequency is within the indicated limits.
Bit 11, No operation/Operation
When bit 11 = "0", the motor does not turn.
When bit 11 = "1", the frequency converter has a start signal, or the output frequency is higher than 0 Hz.
Bit 12, Drive OK/Stopped, autostart
When bit 12 = "0", there is no temporary overloading of the inverter.
When bit 12 = "1", the inverter has stopped due to overloading. However, the frequency converter has not switched off (trip) and will start again after the overloading
has ended.
Bit 13, Voltage OK/Voltage exceeded
When bit 13 = "0", the voltage limits of the frequency converter are not exceeded.
When bit 13 = "1", the direct voltage in the intermediate circuit of the frequency converter is too low or too high.
Bit 14, Torque OK/Torque exceeded
When bit 14 = "0", the motor torque is below the limit selected in par. F-40 Torque Limiter (Driving) and par. F-41 Torque Limiter (Braking). When bit 14 = "1", the
limit selected in par. F-40 Torque Limiter (Driving) or par. F-41 Torque Limiter (Braking) is exceeded.
Bit 15, Timer OK/Timer exceeded
When bit 15 = "0", the timers for the thermal motor protection and electronic overload protection have not exceeded 100%.
When bit 15 = "1", one of the timers has exceeded 100%.