O-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via the
network.
[0]
Digit Input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial communication port or network option module.
[2]
Logic AND
Activates the set-up selection via the network/serial communication port, AND additionally via one of the
digital inputs.
[3] *
Logic OR
Activate the set-up selection via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input) and/
or via the network.
[0]
Digit Input
Activates Preset Reference selection via a digital input.
[1]
Bus
Activates Preset Reference selection via the serial communication port or network option module.
[2]
Logic AND
Activates Preset Reference selection via the network/serial communication port, AND additionally via one
of the digital inputs.
[3] *
Logic OR
Activates the Preset Reference selection via the network/serial communication port OR via one of the
digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-90 Bus Jog 1 Speed
Range:
Function:
100 RPM*
[0 - par. H-13 RPM]
Enter the jog speed. This is a fixed jog speed activated via the serial port or network option.
O-91 Bus Jog 2 Speed
Range:
Function:
200 RPM*
[0 - par. H-13 RPM]
Enter the jog speed. This is a fixed jog speed activated via the serial port or network option.
PB-15 PCD Write Configuration
Array [10]
Option:
Function:
Select the parameters to be assigned to PCD 3 to 10 of the telegrams. The number of available PCDs
depends on the telegram type. The values in PCD 3 to 10 will then be written to the selected parameters
as data values. Alternatively, specify a standard Profibus telegram in par. PB-22 Telegram Selection.
PB-16 PCD Read Configuration
Array [10]
Option:
Function:
Select the parameters to be assigned to PCD 3 to 10 of the telegrams. The number of available PCDs
depends on the telegram type. PCDs 3 to 10 contain the actual data values of the selected parameters.
For standard Profibus telegrams, see par. PB-22 Telegram Selection.