beautypg.com

Connection of supply tubes for dilution bypass gas, Figure 8, Sp2000h/dil/b with control panel dil/s1 – M&C TechGroup SP2000H_DIL_BR Operator's manual User Manual

Page 18

background image

18

Gas sampling and gas conditioning technology

2-1.1.7-ME

Option

–A/A1

When ordering option

–A or -A1, the sets, consisting of pressure regulators and pressure gauges, are

mounted directly on the probe (see Fig.2). Connection of the sample pipe takes place at the elbow
union of the probe (see above).

Option

–S/S1

For option

–S or - S1, the necessary pressure regulators, pressure gauge, shut-off valves and flow

meter are installed externally in a 19“ control panel (see Fig. 4). Connection of the sample or supply
pipes to the probe and downstream analyser system must be established by the customer. Appropri-
ately marked connections are provided at the rear of the 19“ unit.

Test gas

njector-vacuum

Dilution gas

Bypass injector

Open

Open

500 l/h

Check valve

Calibration gas

Dilution gas

Vacuum pressure gauge

Bypass

Control panel DIl/S1

Dilution gas

Cal gas

Sample out

Bypass

Analyser

Figure 8

SP2000H/DIL/B with control panel DIL/S1


13.3

CONNECTION OF SUPPLY TUBES FOR DILUTION BYPASS GAS

Available for connection of the supply tubes are probe-sided tube unions with the dimension
DN4/6mm (1/4“

o

for 115V version). The tube unions are located outside the probe cover and can

be connected without disassembly.

When using option

–A (only dilution gas) or –A1 (dilution and bypass gas), the supply tubes are con-

nected to the unions of the precision pressure regulator.

When using the 19“ control panels, corresponding connections for the supply gases are provided at
the rear of the unit.





Back pressure max. 1,2 bar abs.