beautypg.com

Attach tray power cord, Attach tray power cord -45 – StorageTek 9840 User Manual

Page 95

background image

95741

Sixth Edition

3-45

Rack-mountable Tray

Attach Tray Power Cord

Use the instructions below to attach the power cord between a drive or CSL tray
and the rack power distribution unit (PDU) power strip:

1. Attach the female end of the power cord, part number 10083590, to the AC receptacle on

the tray.

Note: The figure shows the location of the receptacle on a CSL tray. The receptacle on a

drive tray is in a different location.

If you are not using StorageTek RACK001, a different power cord may be required
for the tray.

2. Attach the male end of the power cord to one of the 4-ganged outlets on the rack PDU

power strip.

Note: Earlier deliveries of StorageTek RACK001 may contain a PDU power strip which

has a 6-ganged outlet group.

3. Repeat Step 1 and Step 2 for all remaining CSL or drive trays.

Note: The RACK001 PDU power strip has a maximum of 12 Amps across the ganged

outlets available for powering trays.

The additional, single outlet is reserved for the rack fan power cord.

When installing more than four trays, a second PDU power strip must be obtained
and installed approximately 9 inches above the existing power strip (see

“Install

Optional Second Power Strip” on page 3-29

).

If you have the earlier, 6-ganged outlet PDU power strip, you should limit it to
powering a maximum of four trays, and obtain a second PDU power strip for
additional trays (see

“Install Optional Second Power Strip” on page 3-29

).

4. Slide the power cables into the brackets along the side of the frame.

1. Tray power cord
2. Fan power cord

1

2