Clearing CSL Errors
Refer to the following process to clear CSL errors. Follow the directions
explicitly.
Note: Any time the
operator
indicator is flashing or on solid, clear the obvious
error. Refer to
for a description of the
operator
indicator.
1. After correcting the error, press the
Start
switch (
,
call out 14) to clear the
operator
indicator.
2. If pressing the
Start
switch did not clear the indicator, press the
Start
switch
twice.
Note: Press the
Start
switch twice when there is a load failure or solid
operator
indicator (red) on the CSL. Pressing the switch twice re
initializes the CSL.
3. If pressing the
Start
switch twice did not clear the
operator
indicator, power
cycle the CSL to bring it back online. Refer to
to correctly power cycle the CSL.
shows
the location of the power switch.
4. If power cycling the CSL did not clear the
operator
indicator, the CSL must
be replaced by a qualified technician.
Figure 5-20. CSL Rear View
1.
Power
switch
2. Power cord
3. SCSI cable
4. Terminator