Pilz PSS SB HYD, Basic license User Manual
Page 277
8-41
Modular Block System: Hydraulic Presses
• Block enable
- If the input parameters
NO_1 and NO_2 return to a 1-signal within the
maximum permitted reaction time, the block enable will be triggered
(output parameter
ENBL = 1). This means that the automatic function
test of the ESPE/AOPD has been completed successfully.
The maximum permitted duration of the whole test on Type 2 ESPE/
AOPDs is 150 ms (in accordance with EN 61 496-1 Section 5.2.4, 06/
98).
- If the ESPE/AOPD does not react within the permitted time, the block
enable on the ESPE/AOPD will remain locked (output parameter
ENBL = 0). An error message will appear (see also under “Error
messages” in the SB068 description).
Setting the block parameters
KB1
- SSNR
ESPE-N/O1
- NO_1
ESPE-N/O2
- NO_2
OFF mode = 0
OFF
GdO mode = 1
GdO
SBrk mode = 0
SBrk
DBrk mode = 0
DBrk
Press-ON
- RUN
M 110.00 (RLO-0)
- CyRs
M 110.00 (RLO-0)
- SSeq
M 110.00 (RLO-0)
- ARSt
M 110.00 (RLO-0)
- STyp
UN-signal
- Test
Reset button
- RSET
SB068
BWS_AOS
ENBL - ESPE enabled
TEST - Test input of ESPE emitter
RdCy - Ready to cycle
PWR
- Voltage supply to ESPE
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license