Modular Block System: Hydraulic Presses

6-41

TFbL:

Time for feedback loop monitoring when switching on/off
Permitted value range in ms: 0 ... 2000
When

TFbL = 0, the default value for feedback loop monitoring

will be used from DW1002 of the administration data block
(global parameter

RFbL).

Format: Word constants KF000000 ... KF002000
Recommended value: 100 ms (KF000100)

INFORMATION
The value for feedback loop monitoring should be less than the interval
between consecutive operations.
Irrespective of parameter

TFbL, the initial acknowledgements from

feedback loops

FbL1 =1 and FbL2 = 1 must always be present when

switching on (ON = 0/1 pulse edge).

RSET:

Reset input
RSET = 0/1 pulse edge: trigger reset

Input circuitry
If you are only using one feedback loop, connect the feedback loop input
to

FbL1 and FbL2.

Output parameters

ENBL:

Enable bit
ENBL = 0: Enable is blocked
ENBL = 1: Contactors are free from error

K1:

Output for driving contactor 1

K2:

Output for driving contactor 2

Output circuitry
If you are only using one contactor, connect the contactor output to

K1 and

K2.