Timing diagram, Standard function blocks, Sb069 – Pilz PSS SB HYD, Basic license User Manual
Page 140
6-78
Modular Block System: Hydraulic Presses
Standard Function Blocks
Timing diagram
Legend for diagram:
• Signal level:
The ESPE/AOPD is set to have a guarding function, with start-up and
reset lock.
Input parameters:
SSeq = 0:
Start-up disabler (function test required)
ARSt = 0:
Reset lock
GdOn = 1: Operating mode: ESPE/AOPD has guarding function (guard
only)
Abbreviations:
F-Test
Function test
KoSy
Contact synchronisation time between two N/O contacts
This is a global parameter (see also under “Global parameters”
and SB071).
MTD
Maximum permitted duration of test
(150 ms for type 2 ESPE/AOPDs, in accordance with
EN 61 496-1)
SB069
1-Signal
0-Signal
This manual is related to the following products:
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license