Modular Block System: Hydraulic Presses

Standard Function Blocks

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of DB015 (1st data block), until the fault has been fully dealt

with.

• Error messages in DB015

- Bit 00:

Invalid operation of input parameter

Y1On or Y2On

Remedy: See section entitled “Function”. Once the error has
been rectified, reset (input parameter

RSET)

- Bit 01:

Valve acknowledgement input parameter

S1 remains high after

the valve is switched on
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 02:

Valve acknowledgement input parameter

S1 remains low after

the valve is switched off
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

INFORMATION
If no reaction time has been set for switching off the valve
(

TOff = 0), Bit 02 will remain set until the valve returns to its

start position. This is not a fault, but is important to bear in
mind.

- Bit 03:

Valve acknowledgement input parameter

S1 goes to its start

position during operation (input parameter

S1 goes high while

output parameter

Y1 = 1)

Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 04:

Valve Y1 not in its start position (off) when switched on, i.e.
signal at input parameter

S1 • 1

Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)