6-68

Modular Block System: Hydraulic Presses

Standard Function Blocks

1-Signal
0-Signal

Diagrams for ESPE/AOPD

Legend for diagrams:

• Signal level:

Timing diagram for “guard only” mode of ESPE/AOPD

The ESPE/AOPD is set to have a guarding function with start-up and reset
lock.

Input parameters:
SSeq = 0: Start-up disabler (function test required)

ARSt = 0: No automatic reset of error “ESPE/AOPD interrupted” after the

protected field is cleared (reset lock)

OFF = 0
GdO = 1

Mode: ESPE/AOPD as guard (guard only)

SBrk = 0
DBrk = 0

The input parameters

CyRs, STyp have no effect in “Guard” mode. They

are assigned RLO-0 (M110.00).

Abbreviations:
F-Test

Function test

KoSy

Contact synchronisation time between two N/O contacts
This is a global parameter (see also under “Global parameters”
and SB070).

RBWS

ESPE/AOPD reaction time (150 ms in accordance with EN 61
496-1, 06/98). This is a global parameter (see also under
“Global parameters” and SB070).

SB068