6-68
Modular Block System: Hydraulic Presses
Standard Function Blocks
1-Signal
0-Signal
Diagrams for ESPE/AOPD
Legend for diagrams:
• Signal level:
Timing diagram for “guard only” mode of ESPE/AOPD
The ESPE/AOPD is set to have a guarding function with start-up and reset
lock.
Input parameters:
SSeq = 0: Start-up disabler (function test required)
ARSt = 0: No automatic reset of error “ESPE/AOPD interrupted” after the
protected field is cleared (reset lock)
OFF = 0
GdO = 1
Mode: ESPE/AOPD as guard (guard only)
SBrk = 0
DBrk = 0
The input parameters
CyRs, STyp have no effect in “Guard” mode. They
are assigned RLO-0 (M110.00).
Abbreviations:
F-Test
Function test
KoSy
Contact synchronisation time between two N/O contacts
This is a global parameter (see also under “Global parameters”
and SB070).
RBWS
ESPE/AOPD reaction time (150 ms in accordance with EN 61
496-1, 06/98). This is a global parameter (see also under
“Global parameters” and SB070).
SB068
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license