Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).

S1:

Gate switch: Signal 1

S2:

Gate switch: Signal 2

SyTi:

Synchronisation time between S1 and S2
Value in ms [0 ... 30000]; 0 = infinite time; format: word
constants (KF)

MEin:

Machine is running
MEin = 0:

Machine standing

MEin = 1:

Machine running

MEin = 1/0-pulse edge: Activate reset lock
This parameter can force the operator to carry out a function
test of the gate (gate open/closed).
The reset lock is lifted by carrying out a function test on the
gate followed by the

Strt Signal.

Strt:

Reset input
Strt = 0/1-pulse edge:

- Reset errors OR
- Reset start-up disabler OR
- Reset reset lock

SB 066

ST_K4

B - SSNR
X - S1
X - S2
W - SyTi
X - MEin
X - Strt
X - ARSt
X - AuSt
X - NFkT

FG - X

SB066

If the gate is closed, both gate
switches must supply a 1-signal