Modular Block System: Hydraulic Presses

Standard Function Blocks

- Bit 09:

Hazardous machine functions have not stopped
Although the hazardous machine functions were stopped and
the enable reset, the machine functions are still running.
Remedy: Check standstill monitoring, cable, input card and all
conditions and then reset (when

ARSt = 0)

- Bit 10:

Request to lock safety device when it is still open.
A request was made to lock the gate while the gate was still
open.
Remedy: Close gate or reset (when

ARSt = 0)

- Bit 11:

Gate unlocked
Remedy: Activate guard locking on gate

- Bit 12:

I/O-Group stop triggered while PSS is in RUN mode
Remedy: Start I/O-Group

- Bit 13:

Reset pressed too early
The reset button was operated (

RSET) although at least one

error was still not rectified
Remedy: Press reset button again

- Bit 14:

Reset required
Remedy: Reset

• Error messages on the CPU-display

• E003:

Administration data block has not been initialised

Remedy: Call SB071 in OB120

SB075